Characteristics:
�Voltage adjustment rate < ±1%
�Chosen by toggle switch, single phase
�Detected voltage: 120/240VAC
�Chosen by connecting line: 50/60Hz
�With the function of under-frequency protection and high breaking capacity fuse protection
�With EMI suppression circuit
�1 SE350 and AVC 63-4D is applicable to 220VAC generator without fuse protection device
Technical parameter:
Detected voltage: 120 (90~132) or 240 (171~264) VAC, single phase two wire, chosen by toggle switch
Frequency: 50/60Hz, chosen by connecting line
Output voltage of magnetic field: max voltage 37VDC when input 120VAC, max voltage 74VDC when input 240VAC
Continuous current: 4A
Discontinuous current: 7A within 60s
Resistance: Min 6Ω,Max 100Ω
Voltage adjustment rate < ±1% (the engine speed changed within 4%)
Voltage build-up when the residual magnetism voltage of AVR input terminal is above 3.5VAC
Outside voltage adjustment rate: ±5% (used 1KΩ, 1Watt potentiometer)
±10% (used 2KΩ, 1Watt potentiometer)
Max consumed power: 8Watt
EMI suppression circuit, with electromagnetic interference filter inside
Under-frequency protection: the turning point of 60Hz system is 55Hz; the turning point of 50Hz system is 45Hz (the turning point set when it leaves the factory)
Operation temperature: -40~60â„?/DIV>
Storage temperature: -65~85â„?/DIV>
Relative humidity: below 95%
Vibration: 1.3G @ 5~26Hz, 5.0G @ 52~1000Hz
Special turret:
VOLT: regulate voltage;
STAB: regulate stability
U/F: setting for under-frequency protection
Dimension: 99.5×67.0×47.5 (L×W×H)
Weight: 185g ±2%