DSE702

Features

The DSE702 is available in Manual and Auto Start versions which include all the features of the DSE701 plus a tamper-proof engine hours counter.

KEY FEATURES
•  Manual start and remote start versions
•  Remote start input (auto start version only)
•  Auxiliary shutdown input(Manual start version only)
•  Engine monitoring and protection
•  LED indication
•  Engine pre-heat
•  Tamper proof engine hours
•  Front panel mounting

KEY BENEFITS
•  Hours counter provides accurate information for monitoring maintenance and
warranty periods
• 
Multiple engine parameters are monitored simultaneously

Technical parameters

ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,including Electrical Business Equipment

TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 °C 
BS EN 60068-2-2
Bb/Be Dry Heat +70 °C

VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm, 
8 Hz to 500 Hz @ 2 gn

HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C 
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 °C 

@ 93% RH 48 Hours

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

 

DC SUPPLY
CONTINUOUS VOLTAGE RATING 
8 V to 35 V continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.

OUTPUTS
START
Solid state 1.2 A negative grounding terminal

RUN
Solid state 1.2 A negative grounding terminal

PRE-HEAT
Solid state 1.2 A negative grounding terminal

GENERATOR
VOLTAGE RANGE 
15 V - 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

DIMENSIONS 
DSE702 OVERALL
84 mm x 72 mm x 34.9 mm 
3.3” x 2.8” x 1.4”
Excludes key switch

DSE702 PANEL CUT-OUT 
80 mm x 68 mm
3.1” x 2.7”

MAXIMUM PANEL THICKNESS
8 mm
0.3”