ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 °C
BS EN 60068-2-2
Bb/Be Dry Heat +70 °C
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 °C
@ 93% RH 48 Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
MAXIMUM OPERATING CURRENT
50mA at 12&24V
MAXIMUM STANDBY CURRENT
10mA at 12&24V
ALTERNATOR INPUT RANGE
75V to 333V AC absolute maximum
ALTERNATOR INPUT FREQUENCY
50Hz – 60Hz at rated engine speed(minimum:75V AC L-N)
OUTPUTS
START & RUN OUTPUT
1.2 Amp DC at supply voltage.Switches to battery negative when active
CLOSE GEN/MAINS (UTILITY) CONTROL OUTPUTS
1.2 Amp DC at supply voltage.Switches to battery negative when active
AUXILIARY OUTPUTS
1.2 Amp DC at supply voltage.Switches to battery negative when active
DIMENSIONS
DSE705 OVERALL
165 mm x 125 mm x 29 mm
6.5” x 4.9” x 1.2”
DSE705 PANEL CUT-OUT
149 mm x 149 mm
5.9” x 4.3”
STORAGE TEMPERATURE RANGE
-40°C to +85°C