DC SUPPLY
8 V to 35V continuous
CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V. This is achieved without the need for internal batteries.
MAXIMUM OPERATING CURRENT
180mA at 12V,190mA at 24V
TYPICAL CURRENT
145mA at 12V,150mA at 24V
GENERATOR INPUT RANGE
35V(L-N) to 333V AC (L-N) absolute maximum
50Hz – 60Hz (min 15V AC)
AUXILIARY OUTPUTS
Solid state
2.4A DC at supply voltage
FUEL/START OUTPUTS
Solid state
3.4A DC at supply voltage
GENERATOR C.T.
5A secondary 0.5VA
MAINS (UTILITY) SENSING INPUT RANGE
35V(L-N) to 333V AC (L-N) absolute maximum
50Hz – 60Hz (min 15V AC)
DSE720 DIMENSIONS
209mm x 146mm x 30.3mm
8.2” x 5.7” x 1.2”
DSE720 CUT OUT
182mm X 137mm
7.2” x 5.4”
MAXIMUM PANEL THICKNESS
8 mm
0.3”
ENVIRONMENTAL TESTING STANDARDS
ELECTRO MAGNETIC CAPABILITY
BS EN 61000-6-2
EMC Generic Emission Standard for the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-2
Test Ab to +70°C 60067-2-2 Hot
Test Ab to -30°C 60068-2-1 Cold
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5Hz to 8Hz @ +/-7.5mm,8Hz to 500Hz @ 2gn
HUMIDITY
BS 2011 part 2.1 60068-2-30
Test Cb Ob Cyclic
93% RH @ 40°C for 48 hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15gn in 11mS