Voltage 220/380/440 VAC, 3 phase 3 wire Frequency 50/60 Hz selectable |
Power Input |
Voltage 100~300 VAC, 1 phase 2 wire |
Output |
Voltage Max. 90 VDC @ 240 VAC input Current Continuous 15A, Intermittent 20A for 10 sec. Resistance Min. 4Ω @ 35 volts output |
Volts Regulation |
< ±0.5% (with 4% engine governing) |
Voltage Build-up |
Residual volt. at AVR terminal > 5 VAC |
External Volts Adjustment |
±15% with 5 KΩ 1 watt trimmer |
Unit Power Dissipation |
Max. 8 watt |
Soft Start Ramp Time |
2 sec. |
Thermal Drift |
0.03% per °C change in AVR ambient |
Under Frequency Protection |
60 Hz system presets knee point at 55 Hz 50 Hz system presets knee point at 45 Hz |
Environment |
Operating Temperature : -40~65 °C Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
AVR Controls Functions |
VOLTS : Voltage Adjustment STAB : Stability Adjustment U/F*: To Set the U/F Knee Point (*U/F: Under Frequency Protection) |
Dimensions |
150.0 (L) x 135.0 (W) x 72.0 (H) mm |
Weight |
867 g ±2% |